The following are the unit Data and operation parameters:Ģ- Discharge operating pressure up to 230 Psig.ģ- Oil Pressure always 4 to 8 psid below discharge pressure due to oil filter differential.

Or I enter the capacity calibration screen and press unload capacity then it works and slide valve start moves to unloading position. Unless I stop it while it is at 100% FLA, the slide goes to 0 position.

I am facing a problem with XJF 120 Compressor as it loads perfect but once it load above 75 or 80 % of the FLA and we try to unload it manually or even Auto it never unload.